mapping planned support spacing to the most suitable composite panel family for an industrial deck, independent of surface appearance
- Sort candidate sections by the planned span before comparing surface or color.
- Molded panels distribute load across an interwoven mesh and suit moderate spans and general walkways.
- Pultruded T-bar and I-bar profiles carry load along continuous bars and suit longer or stiffer spans.
1. Scope and Engineering Context
Matching a deck to the right composite family starts with the planned support spacing, because molded panels and pultruded profiles carry bending in different ways. A molded panel spreads pedestrian load across an interwoven mesh, while a pultruded T-bar or I-bar relies on continuous bars running between bearings. Sorting sections by span first keeps the choice away from colour, resin tint or surface pattern.
The preliminary comparison should record how far apart the supports sit, the deflection limit written into the specification, and whether the deck is a passing walkway or a standing platform. Those three facts point toward a family before any mesh size or bar depth is debated.
- molded panel. A panel formed with interwoven continuous filaments and a molded grid; it distributes load across the mesh and suits moderate, closely spaced supports.
- pultruded profile. A profile pulled through a die, supplied as T-bar or I-bar; load travels along the continuous bar, which suits longer or stiffer decks.
- span range. The band of bearing spacings a given section is considered for in preliminary selection, taken from the tabulated 600/900/1200 mm rows.
- stiffness. Resistance to bending and sag under the design duty, checked against the contract deflection limit rather than judged by how firm the deck feels.
- mesh vs bar. The trade between an interwoven mesh and a directional bar; mesh influences open area and local spreading, while bars set the spanning stiffness.
2. Worked Example and Site Checklist
Compare allowable load at the same real spacing to separate the families. At a 900 mm simply supported span, Molded 38 mm allows 12 kN/m², Pultruded 38 mm allows 18 kN/m²; over 1200 mm the molded row drops to 6.5 kN/m² while the pultruded 38 mm row reaches 9 kN/m². The gap widens as supports move apart, which is why longer decks lean on continuous bars rather than mesh panels.
For an imperial cross-check, the 18 kN/m² pultruded 38 mm figure at 900 mm converts to about 376 lb/ft² (18 × 20.9), and the molded 12 kN/m² to about 251 lb/ft². These are preliminary table references; the governing design load and any tighter deflection limit come from the project specification, not the catalogue.
| Check on site | What to record | Why it matters |
|---|---|---|
| Sort candidates by planned span | List each family against the real bearing spacing | Family comparison before finish avoids a section picked for the wrong reason. |
| Note how load spreads on the deck | Record whether pedestrians, tools or staged equipment occupy it | Mesh spread matters for general walkways; continuous bars matter for longer duty. |
| Write down the deflection limit | Copy the L/200, L/360 or other limit from the specification | A tighter limit lowers the usable load and can push the choice to a deeper profile. |
| Leave borderline spacings open | Flag spans near the edge of a tabulated range for confirmation | A marginal span should be matched to a report rather than assumed adequate. |
| Check mesh only after family and depth | Record open area or pattern once the bar type is fixed | Mesh changes local spreading; it does not by itself extend a panel's span. |
| Item | Verified figure / note |
|---|---|
| Molded 38 mm @ 900 mm | 12 kN/m² allowable UDL |
| Pultruded 38 mm @ 900 mm | 18 kN/m² allowable UDL |
| Molded 38 mm @ 1200 mm | 6.5 kN/m² allowable UDL |
| Pultruded 38 mm @ 1200 mm | 9 kN/m² allowable UDL |
3. Failure Modes and Cautions
A recurring counterexample is carrying a molded rating past its practical span: a panel adequate on closely spaced supports is continued over a wider run where the mesh cannot keep sag within the limit. The closer-spacing figure must not be reused once bearing spacing changes; the section has to be re-read at the new span.
Another mistake is choosing a pultruded profile for a short walkway merely because it looks heavier. A deeper bar adds weight and cost without a duty that justifies it; over-specification here shows up as unnecessary framing load and handling effort.
- Compare allowable load at the actual span, not strength implied by bar depth or panel appearance.
- Mesh size, open area and surface pattern follow the family decision; they do not override the spanning requirement.
- State support spacing, design duty, deflection limit and any rolling load in the RFQ so the recommendation is checked against the correct series.
4. Boundary: When This Does Not Apply
This family comparison covers preliminary uniform-load selection only. It does not settle concentrated or point loads, wheeled traffic, cantilevered ends, impact, repeated fatigue, wind uplift, seismic fixing, or temperature-related derating; those cases require an independent stamped structural review.
Where two decks share one approach but carry different duties, do not force a single family across both; size each area for its more severe condition. A panel selected from a short-span walkway row should not be extrapolated onto a long platform without the engineer's matched calculation.
5. Frequently Asked Questions
Which grating family is better for shorter spans?
Molded panels are commonly adequate on moderate, closely spaced supports; their interwoven mesh distributes pedestrian load across the deck. The final choice still follows the table at the actual span.
When does pultruded become the better option?
Pultruded profiles are typically considered for longer spans, deeper bars or stiffer platform duty, where continuous bars provide the needed stiffness. T-bar suits walkways; I-bar serves longer heavy platforms.
Does mesh size change the span recommendation?
Mesh affects open area, surface pattern and local load spreading, but span selection starts from bar depth and profile type. Compare mesh only after the family and depth are set.
Can a molded panel reach a long span?
Within the tabulated range molded sections cover their listed spans; beyond that, or under heavier duty, a pultruded deeper section may be more suitable. Do not extend a molded rating past the table.
What should the RFQ state for family selection?
State support spacing, design duty, deflection limit and any rolling or equipment load, so the recommendation can be checked against the correct table and profile series.