FRP Grating Span and Load Calculator
Enter the clear span between supports and read the allowable uniform load for the construction you are specifying. The figures come from the load table we publish, at roughly 1% of span deflection, and the tool interpolates between table points instead of inventing numbers.
The published load table
These are the same figures as the product page, so the calculator cannot drift away from what the site states. Allowable uniform loads are given at 600, 900 and 1200 mm clear span, for a deflection of about 1% of the span.
| Construction | 600 mm span | 900 mm span | 1200 mm span |
|---|---|---|---|
| Molded 25 mm, 38 x 38 | 12.5 kN/m² | 6.0 kN/m² | 3.2 kN/m² |
| Molded 38 mm, 38 x 38 | 25 kN/m² | 12 kN/m² | 6.5 kN/m² |
| Molded 38 mm, 50 x 50 | 22 kN/m² | 10 kN/m² | 5.5 kN/m² |
| Pultruded I-bar 38 mm | 35 kN/m² | 18 kN/m² | 9 kN/m² |
| Pultruded I-bar 50 mm | 48 kN/m² | 26 kN/m² | 14 kN/m² |
| Pultruded I-bar 65 mm | 62 kN/m² | 35 kN/m² | 20 kN/m² |
Check your span
Span and load check
Enter the clear span between supports. The tool reads the published table and tells you the allowable uniform load at that span.
The figure is an allowable uniform load at roughly 1% of span deflection. It is not a point-load rating and it is not a stamped design. Where the answer decides safety, the design is signed by an engineer against the actual support conditions.
Reading the number correctly
The table is a uniform load figure at a fixed deflection, not a breaking load. Doubling the span roughly quarters the allowable uniform load, which is why the drop from 600 mm to 1200 mm looks so steep on every row.
Two limits sit behind every figure. Strength decides whether the panel survives, and deflection decides whether it feels like a floor. On walkways the deflection limit usually governs, because a panel that carries the load but sags visibly under a boot gets rejected on site no matter what the calculation says.
A 1% deflection limit is the common industrial basis. A pedestrian walkway in a public or food area is sometimes held to a tighter limit, and a platform carrying trolleys or pallets is often allowed more. State the limit you are designing to, because it changes the answer more than the load does.
What the table cannot tell you
- Point loads. A 1.5 kN concentrated load from a trolley wheel or a ladder foot is a different check from a uniform load, and it needs the bar section and the load position. Send the load case and we will run it.
- Support conditions. The table assumes the panel simply rests on supports with the bearing length the panel needs. A panel overhanging a beam, or resting on two thin rails, is not the same structure.
- Load duration and temperature. A resin panel at 80 degrees C in a chemical plant does not carry what it carries at 20 degrees C in a warehouse.
- Fatigue and impact. Repeated forklift traffic and dropped tools are not in any static table.
- Fire. A load table says nothing about behaviour in a fire, and no FRP panel is a fire-rated floor without a tested system behind it.
How a real design is settled
The path that ends with a safe deck is short: the support grid is fixed by the steel, the span is read off it, the load case is agreed with the client, and the panel is selected from the table with a margin. What the table gives you is a defensible starting point and a way to see quickly that a 1200 mm span in 25 mm grating will not do for a 5 kN/m2 walkway.
Where the answer decides safety, the design is signed by an engineer against the actual support layout. Our role is to supply the section properties, the tested reports and the panels that match them, and to say plainly when a span is outside what we have tested.