Tool

FRP Grating Span and Load Calculator

Enter the clear span between supports and read the allowable uniform load for the construction you are specifying. The figures come from the load table we publish, at roughly 1% of span deflection, and the tool interpolates between table points instead of inventing numbers.

The published load table

These are the same figures as the product page, so the calculator cannot drift away from what the site states. Allowable uniform loads are given at 600, 900 and 1200 mm clear span, for a deflection of about 1% of the span.

Construction600 mm span900 mm span1200 mm span
Molded 25 mm, 38 x 3812.5 kN/m²6.0 kN/m²3.2 kN/m²
Molded 38 mm, 38 x 3825 kN/m²12 kN/m²6.5 kN/m²
Molded 38 mm, 50 x 5022 kN/m²10 kN/m²5.5 kN/m²
Pultruded I-bar 38 mm35 kN/m²18 kN/m²9 kN/m²
Pultruded I-bar 50 mm48 kN/m²26 kN/m²14 kN/m²
Pultruded I-bar 65 mm62 kN/m²35 kN/m²20 kN/m²

Check your span

Span and load check

Enter the clear span between supports. The tool reads the published table and tells you the allowable uniform load at that span.

The figure is an allowable uniform load at roughly 1% of span deflection. It is not a point-load rating and it is not a stamped design. Where the answer decides safety, the design is signed by an engineer against the actual support conditions.

Reading the number correctly

The table is a uniform load figure at a fixed deflection, not a breaking load. Doubling the span roughly quarters the allowable uniform load, which is why the drop from 600 mm to 1200 mm looks so steep on every row.

Two limits sit behind every figure. Strength decides whether the panel survives, and deflection decides whether it feels like a floor. On walkways the deflection limit usually governs, because a panel that carries the load but sags visibly under a boot gets rejected on site no matter what the calculation says.

A 1% deflection limit is the common industrial basis. A pedestrian walkway in a public or food area is sometimes held to a tighter limit, and a platform carrying trolleys or pallets is often allowed more. State the limit you are designing to, because it changes the answer more than the load does.

What the table cannot tell you

  • Point loads. A 1.5 kN concentrated load from a trolley wheel or a ladder foot is a different check from a uniform load, and it needs the bar section and the load position. Send the load case and we will run it.
  • Support conditions. The table assumes the panel simply rests on supports with the bearing length the panel needs. A panel overhanging a beam, or resting on two thin rails, is not the same structure.
  • Load duration and temperature. A resin panel at 80 degrees C in a chemical plant does not carry what it carries at 20 degrees C in a warehouse.
  • Fatigue and impact. Repeated forklift traffic and dropped tools are not in any static table.
  • Fire. A load table says nothing about behaviour in a fire, and no FRP panel is a fire-rated floor without a tested system behind it.

How a real design is settled

The path that ends with a safe deck is short: the support grid is fixed by the steel, the span is read off it, the load case is agreed with the client, and the panel is selected from the table with a margin. What the table gives you is a defensible starting point and a way to see quickly that a 1200 mm span in 25 mm grating will not do for a 5 kN/m2 walkway.

Where the answer decides safety, the design is signed by an engineer against the actual support layout. Our role is to supply the section properties, the tested reports and the panels that match them, and to say plainly when a span is outside what we have tested.

Related pages

FAQ

What span can FRP grating cover without support?
For a normal walkway load, 38 mm molded grating is comfortable to about 900 mm clear span and marginal at 1200 mm; pultruded I-bar 50 mm carries 26 kN/m2 at 900 mm and 14 kN/m2 at 1200 mm. The calculator shows the exact table figure for your span.
Is the table figure a safe working load or a breaking load?
A safe working load at a deflection of about 1% of span. The breaking load is several times higher, and it is not what you should design to.
Why does doubling the span cut the allowable load so much?
Because deflection rises with the fourth power of span for a uniformly loaded beam, and bending stress rises with the square. That is why the table drops steeply and why adding a support beam is usually cheaper than buying thicker grating.
Can I use the calculator for a point load?
No. Point loads need the bar section, the load position and the bearing detail. Send the load case, for example a 1.5 kN wheel load, and we will run the check.
Does temperature reduce the allowable load?
Yes. Resin softens as temperature rises, and the reduction depends on the resin system. Above the service temperature of the grade you are buying, the table figure no longer applies.
Which is stronger, molded or pultruded grating?
Pultruded, in the load direction, because the bars are continuous and carry the load along their length. Molded grating is balanced in both directions and better suited to panels that are handled and cut on site.

Document Preview

Preview mode · For full document, click Download

Download Document

Thank you for your interest. Please fill in your email and company name. Our technical and sales team will contact you within 30 minutes (during working hours) to provide support!

📧 Your information will be sent to [email protected]. We respect your privacy and will never share your data.

Thank You!

Your request has been received successfully.

Our technical and sales team will contact you within 30 minutes (during working hours) to provide the document and professional support!

If you need urgent assistance, please email: [email protected]