60% Open Area Pultruded FRP Grating
Maximum clear opening for drainage, airflow and lightness: the deck for wet channels, cooling air and spray areas.
Technical specifications
| Type | Pultruded FRP grating, open bar layout |
|---|---|
| Bearing bar depth | 25 mm or 38 mm |
| Bar pitch | 38 mm with a clear opening of about 23 mm |
| Open area | about 60% |
| Unit weight | about 7.5 kg/m² at 25 mm depth; about 12.5 kg/m² at 38 mm depth |
| Standard panel | 1220 x 3660 mm, cut to size |
| Resin systems | Isophthalic polyester; vinyl ester for wet chemical service |
| Surface | Concave, grit, or smooth |
| Fixing | Standard clip family; SS316 in chloride or acid spray |
| Typical duty | Drainage covers, cooling air inlets, spray zones, light walkways |
Load and span guidance
| Support span | Indicative UDL, 25 mm depth | Indicative UDL, 38 mm depth | Deflection basis |
|---|---|---|---|
| 1.5 m | about 450 kg/m² | about 500 kg/m² | L/200 |
| 2.0 m | about 250 kg/m² | about 315 kg/m² | L/200 |
| 2.5 m | about 150 kg/m² | about 210 kg/m² | L/200 |
| 3.0 m | about 95 kg/m² | about 145 kg/m² | L/200 |
Indicative values for one simply supported span under uniform load. The open layout carries less load than a dense one at the same depth, which is the price of drainage. Certified values come from the project load table.
Open area as a design requirement
Where water has to leave a deck quickly, open area is the specification. Sixty percent clear opening passes a heavy rainfall and a hose-down flow without ponding, and it lets cooling air rise through a walkway instead of blanking it off. On a cooling tower or an air inlet plenum the deck is effectively part of the air path, so a dense grating would change the thermal performance of the plant rather than just its appearance.
The section also stays light. At 7.5 kg/m² for the 25 mm version, a full panel weighs about 33 kg, which is a one-person carry on a service route and a small load on a long span. The trade-off is a deck that will not stop a dropped tool, so where both drainage and drop-through protection matter we split the deck, open over the channel and dense over the walkway.
Where it fits
- Drainage and overflow channel covers in water works
- Cooling tower decks and air inlet plenums
- Spray and wash-down zones in food and chemical plants
- Light footbridges and inspection walkways over water
- Screen and filter support decks in effluent treatment
High open area panels should not be walked on with sharp-heeled footwear before the surface is verified; concave bars give a wider contact than smooth ones. Clips at panel edges are spaced more closely because the open panel is more flexible.